Description
KJ1501X1-BB1 EMERSON Central control module
Product Dimensions:
Product Description
The KJ1501X1-BB1 acts as the primary power interface for a DeltaV controller and I/O node. It converts bulk 24V DC input into a regulated 12.25V DC output that flows through the backplane (carrier) to energize the internal logic of the controllers and I/O modules. The “BB” series is a standard reliability power supply that forms the backbone of many legacy and mid-generation M-series installations.
Product Parameters
| Feature | Specification |
| Model Number | KJ1501X1-BB1 (VE4002S1T2B2) |
| Input Voltage | 24V DC (±10%) |
| Input Current | 5.2 Amps (Maximum) |
| Output Voltage | 12.25V DC |
| Output Current | 13.0 Amps (Maximum load per carrier) |
| Power Dissipation | 10.0 Watts |
| Operating Temperature | 0°C to +60°C (32°F to +140°F) |
| Storage Temperature | -40°C to +85°C (-40°F to +185°F) |
| Mounting | DeltaV 2-wide Power/Controller Carrier |
| Hazardous Area Rating | Class I, Div 2; ATEX II 3G |
Product Advantages
-
Seamless Redundancy: Two modules can be used on a redundant carrier to provide “fault-tolerant” power. If one BB1 fails, the other takes over instantly without affecting the controller’s operation.
-
Integrated Diagnostics: The DeltaV system monitors the health of the BB1 module. Faults such as “Power Supply Failed” or “Low Input Voltage” are reported directly to the operator’s alarm console.
-
Compact Design: Occupies very little space on the rail, allowing for more I/O modules to be placed within the same cabinet.
-
Easy Installation: Uses the DeltaV “snap-in” mechanism, making it simple to install or replace without the need for manual wiring at the module itself.
-
Cost-Effective: Provides a reliable power solution for standard industrial environments that do not require the extreme temperature ratings of the “BC” series.
Important Considerations & Precautions
-
Temperature Limits: Unlike the newer “BC” series (which goes up to 70°C), the BB1 is typically rated for 60°C. Ensure your cabinet cooling is sufficient for this range.
-
Input Polarity: Ensure the 24V DC input wiring to the carrier is correctly polarized; reversed polarity can blow internal non-replaceable fuses.
-
LocalBus Load: Do not exceed the 13 Amp limit of the LocalBus. While one power supply can handle many modules, high-density I/O configurations should be calculated during design.
-
Hot-Swap Safety: In hazardous environments (Class I Div 2), always ensure the area is non-explosive before “hot-swapping” the module, as small arcs may occur during insertion.
Product Applications
-
Batch & Continuous Control: Used across the chemical and pharmaceutical industries to power DeltaV MD or MQ controllers.
-
Manufacturing Plants: Providing power to I/O racks for automotive or consumer goods assembly lines.
-
Legacy System Support: Frequently used as a replacement part for older DeltaV M-series systems that were originally commissioned with BB-series hardware.
-
Control Room Cabinets: Ideal for indoor, climate-controlled environments where the extreme ruggedization of the “BC” series is not required.
Shipping Port: Xiamen, China
Payment: Bank of Chicago, Bank of Singapore
Express cooperation: fedex, DHL, UPS and your express account
Service: Professional Sales provides 24 hours /7 days online service
Please make an inquiry for more models:
| A6110 | EMERSON | KJ3006X1-BA1 | EMERSON |
| 211001BNA | EMERSON | KJ4001X1-CJ1 | EMERSON |
| VE4005S2B2 | EMERSON | VE4003S2B3 | EMERSON |
| RRE5009 | EMERSON | KJ3101X1-BB1 | EMERSON |
| 5X00070G01 | EMERSON | SLS1508 | EMERSON |
| A6110 | EMERSON | VE4001S2T2B1 | EMERSON |
| A6210 | EMERSON | VE4001S2T2B4 | EMERSON |
| A6312 | EMERSON | VE4002S1T2B1 | EMERSON |
| HART 475 | EMERSON | VE4002S1T2B5 | EMERSON |
| 211001BNA | EMERSON | VE4003S2B1 | EMERSON |
| EC3-X33 | EMERSON | VE4003S2B3 | EMERSON |
| 396572-04-9 | Emerson | 5X00070G01 | EMERSON |
| 12P2471X042 | EMERSON | 1B30035H01 | EMERSON |
| 12P3904X022 | EMERSON | 1C31132G01 | EMERSON |
| 12P3439X012 | EMERSON | 1C31129G03 | EMERSON |
| 00475-1130 | EMERSON | VE5009 | EMERSON |
| 1C31116G04 | EMERSON | 5X00119G01 | EMERSON |
| 5X00502G01 | EMERSON | 5X00121G01 | EMERSON |
| 5X00070G04 | EMERSON | 1C31129G03 | EMERSON |
| FLUXUS F721 | EMERSON | 1C31132G01 | EMERSON |
| 396657-01-0 | EMERSON | 5X00357G04 | EMERSON |
| 5X00062G01 | EMERSON | 5X00497G01 | EMERSON |
| 1X01046H01L | EMERSON | 5X00070G04 | EMERSON |
| FB3000 | EMERSON | 1C31116G04 | EMERSON |
| 1C31194G03 | EMERSON | KJ3243X1-BB2.1 + KJ3007X1-EA1.2 | Emerson |
| SS6501T01 | EMERSON | 33B7073X032 | EMERSON |
| 1X01046H01L | EMERSON | A6210 | EMERSON |
| SKC3400400 | EMERSON | A6630 | EMERSON |



Phone:
Email:
WhatsApp: